All products on this website are discounted products, and market prices have been fluctuating. Please refer to customer service quotes for details. Pictures are not actual photos. Before placing an order, please confirm the model, product, price, and other detailed information with customer service. Both second-hand and brand new products are available for sale on this website. Please contact customer service for further communication.
HIMA F8652X|CPU Module|

System Adaptation
This safety CPU is designed for HIMA H41q and H51q-MS / HS / HRS safety control systems.
It requires Operating System V7.0-7 or later and operates as the primary / backup processor in rack-based SIS and ESD architectures.
Key Specifications
Processor Architecture
Dual Intel 386EX 32-bit processors
Lockstep, clock-synchronized operation
Clock frequency: 25 MHz
Memory Configuration
System Flash: 1 MB
User Program Flash: 1 MB
Data SRAM: 1 MB
Communication Interfaces
2 × electrically isolated RS-485
Selectable baud rates: 9.6 / 57.6 kbit/s
Supports Modbus RTU / ASCII
Communication expansion via:
F8627X Ethernet coprocessor
F8628X PROFIBUS DP coprocessor
Diagnostics & Safety Outputs
4-digit matrix display
LED status indicators
Fault-safety watchdog output:
24 V DC, max. 500 mA
Short-circuit protected
Power Supply & Consumption
Power supply: 5 V DC / 2 A, provided by F7300A power module
Typical power consumption: approx. 5 W
Mechanical & Environmental
Mounting: 19-inch rack
Width: 8 SU
Operating temperature: −20 °C to +60 °C
Supports hot swapping
Core Functionality
Redundant Safety Computation
Dual CPUs operate in clock-synchronized lockstep with continuous cross-checking, enabling fast fault detection and deterministic fault-safe behavior.
System Control Center
Acts as the central safety processor, coordinating:
Safety I/O modules (F6217, F6706)
Communication coprocessors (F8627X, F8628X)
Execution of safety logic, interlocks, and shutdown functions
Comprehensive Diagnostics
Real-time monitoring of:
Supply voltage
Temperature
Communication status
Memory integrity
Supports rapid fault localization, reset, and recovery.
Configuration & Maintenance
Engineered via ELOP II
Supports dual-machine hot standby
Online diagnostics
Hot-plug maintenance without system shutdown
Redundancy & Expansion
Redundant Architecture
Dual-machine hot standby
Primary / backup CPU configuration
Can be combined with F8650X / F8650E to form a highly available and fault-tolerant safety system
Expandable Components
F8627X – Ethernet communication coprocessor
F8628X – PROFIBUS DP communication coprocessor
F6217 / F6706 – Safety I/O modules
Typical Applications
Used in safety-critical industrial systems, including:
Petrochemical and chemical plants
Offshore oil & gas installations
Power generation facilities
Metallurgy and heavy industry
Typical safety functions include:
Process emergency shutdown (ESD)
Unit and equipment protection
Safety interlocking